Performance Qualification of WFI, Purpose
Performance Qualification of WFI, To authenticate and document that the performance of the WFI Generation and Distribution System installed at the WFI & PS plant room (roof top) of Cephalosporin Block of XX Pharmaceuticals Limited is satisfactory in all critical features related to the operational requirements during Phase – 3 study.
Performance Qualification of WFI, Scope
This protocol will be applicable for performing Phase – 3 validation study to verify that the Water For Injection generation and distribution system installed at WFI & PS plant room (roof top) of Cephalosporin Block of XX Pharmaceuticals Limited consistently produce desired quality of Water For Injection over the study period of 01 year.
People also Read
Water For Injection Performance Qualification of Phase 2 Study
Responsibilities
[][]Preparation of the protocol
Validation (Engineering) Department.
[][]Executing the protocol
Validation team along with respective departmental person and engineers or other suitably qualified staff allocated from the site or contracted specialists as appropriate.
[][]Chemical test
Quality Control Department
[][]Microbiological Test
Microbiology Department
[][]Data documentation and preparation of the report
Validation (Engineering) department.
[][]Verifying the report
Concerned departmental person.
[][]Providing documentation on the equipment
Related departments i.e. Engineering, Quality Control, Microbiology, Validation.
System And Process Description
System Information
=>Manufacturer : Watertown
=>Capacity : 750 ltr/hr
=>Model : MS750/4T
=>Manufacturer no. : MS1132
The System under test
[][]The Water For Injection system is designed to generate and distribute the desired quantity & quality of Water For Injection to various user points.
Generation system of Water For Injection
[][]The WFI production process consists of purified water evaporation followed by pure steam separation and condensation through four multi-effect water still columns.
[][]Purified water from the storage tank is pressurized through a feed water pump and pre heated in the four pre heaters.
[][]Then, the purified water becomes pure steam in the four multi effect columns by exchanging heat with the plant steam.
[][]There are two condensers in the system. The first condenser is used to cool the pure steam by exchanging heat with the incoming feed water (PW).
[][]Finally, the WFI is produced in second condenser by exchanging heat with the chilled water which is then supplied to the WFI storage tank.
Distribution system of Water For Injection
[][]The WFI is stored in a WFI storage tank of 2000 ltr capacity and is distributed to the user points and circulated within a loop by a high pressure pump.
[][]There is a heat exchanger in the distribution section to sterilize the whole distribution system.
Tests To Be Performed And Sampling Plan
[][]A comprehensive validation study plan has been established where a weekly sampling plan has been developed for Phase-3 study of WFI system for 01 year concerning weekly testing of all main sampling points.
[][]The sampling will be taken one day a week on working days. The acceptance criterion of the tests are stated in the table.
Main Sampling Points
The sampling points of WFI are listed below:
Sl. No. | Sample ID | User point Location | Tests | Microbial Count/ Chemical Tests |
---|---|---|---|---|
01 | WSP-1 | Final WFI after condenser – 2 (before WFI storage tank). | Next Table | Weekly |
02 | WSP-2 | At supply of WFI Distribution Loop | Next Table | Weekly |
03 | WSP-3 | At return of WFI Distribution Loop | Next Table | Weekly |
04 | WUSP – 01 | WFI Distribution Loop | Next Table | Weekly |
05 | WUSP – 02 | WFI Distribution Loop | Next Table | Weekly |
06 | WUSP – 03 | WFI Distribution Loop | Next Table | Weekly |
07 | WUSP – 04 | Cold User point | Next Table | Weekly |
Tests and Acceptance Criteria for Water for Injection
Sl. No. | Tests | Frequency | Acceptance Criteria | Alert Limit | Action Limit |
---|---|---|---|---|---|
01 | Appearance | Daily from each sampling point. | Clear, colorless and odorless liquid. | N/A | N/A |
02 | Conductivity | Daily from each sampling point. | Not more than 1.1 µS/cm at 20⁰C or Not more than 1.3 µS/cm at 25⁰C | 0.7 µS/cm | 0.9 µS/cm |
03 | Total Organic Carbon | Daily from each sampling point. | Not more than 500 ppb | 106.4 ppb | 135.8 ppb |
04 | Total Viable Microbial Count | Daily from each sampling point. | Not more than 10 CFU/100 mL | 5 CFU/100 mL | 8 CFU/100 mL |
05 | E.coli | Daily from each sampling point. | Must be Absent | N/A | N/A |
06 | Staphylococcus aureus | Daily from each sampling point. | Must be Absent | N/A | N/A |
07 | Pseudomonas aeruginosa | Daily from each sampling point. | Must be Absent | N/A | N/A |
08 | Salmonella spp | Daily from each sampling point. | Must be Absent | N/A | N/A |
09 | Bacterial Endotoxins | Daily from each sampling point. | Less than 0.25 EU /mL | N/A | N/A |
[][]Performance Qualification shall be considered acceptable when all the conditions above have been met.
[][]Any deviation from the acceptance criteria of the specific check point shall be reported and decision should be taken for the rejection, replacement or rectification of the equipment/component/system.
Conclusion
[][]The results of the Phase – 3 study, as per the qualification protocol are recorded & analyzed.
[][]The observed parameters/tests and subsequent analytical results show that the Water For Injection Generation and Distribution System Complies/Does Not Comply as per the predetermined acceptance criteria.
[][]Hence, the Water For Injection Generation and Distribution is / is not qualifying the Phase – 3 study of Performance Qualification and the System can be / cannot be used for production purpose and continued to regular monitoring by Quality Control and Microbiology department.
Download Here
Performance Qualification Protocol of WFI Phase 3